IEC 104 Server / Configuring IEC 104 Server
In this video of our N3uron Academy, we explain the N3uron IEC 104 Server configuration, using data from a photovoltaic plant. Let’s get started!
[10:20] Configuring IEC 104 Server
[00:00] Hello everyone! In this video, we explain the N3uron IEC 104 Server configuration, using data from a photovoltaic plant. This Web Vision HMI shows key performance indicators, or KPIs. We will expose values such as power, energy, and performance ratio through IEC 104. Here are the plant tags in the real-time view. We also created a Boolean tag for a single command from an IEC 104 client. In our example, the client is an RTAC controller from SEL, Schweitzer Engineering Laboratories. We start with a new module instance in the Modules configuration.
[01:00] We give it a name, select IEC 104 Server as the module type, and save it. The instance then appears in the Explorer panel. Its configuration has a Model panel for the running configuration and a Templates panel for reusable definitions. We create Server one inside the Model panel in this case. This level contains the network connection settings. Our server listens on all interfaces, on TCP port twenty-four oh four. The adapter browser also lets us select a specific network interface. For this example, we allow one client connection. This is a setting for this server. When we select a property, the quick help below explains its purpose and the available values. The timing settings control how long the server waits for acknowledgements and when it checks an idle connection.
[02:01] K limits messages sent without an acknowledgement. W controls when received messages are acknowledged. We keep the values shown in this example. Next, we create Device one under the server. A device represents a logical station within this connection. Its common address identifies that station. In our example, the first device uses address one. For events, we use Long time, which includes the full date and time. The other choices are Short time and None. Each device can use its own format. Commands sent to this server must use supported command types in Direct Execute mode. Information object groups help us organize the configuration. We name this group Plant KPIs because it contains the points that we want to expose for the plant.
[03:01] Other projects can group their points around their own equipment or application. Inside the group, our first information object is active energy day. The tag browser shows the existing plant model. We select the daily energy tag here, so the information object uses this value. N3uron keeps this part of the configuration simple. We choose the type of value, such as Floating point or Single point. N3uron then uses the correct supported ASDU, which is the message type used by the protocol. That choice is transparent to the user. We choose Floating point under read. Commands are under Write. For events, the timestamp mode also affects the message type. The quick help explains the details. The information object address identifies the point within the device.
[04:00] Our daily energy measurement uses address one. An interrogation is a request for data. A numbered group lets the server return a selected set of points. Here, we leave the setting at None. The point still takes part in General Interrogation and sends events when its value changes. We also add an information object for the command. This one uses the Boolean tag that we prepared earlier. The same tag browser lets us select it from the data model, alongside the existing measurement tags. This uses Single point command, under Write, and address eleven. We save the configuration and accept the module restart to apply these changes. Here we see the command tag itself. Its access mode allows reading and writing, so the server can write the received command to this tag. The real-time view shows it beside the plant measurements.
[05:01] This gives us a view of the source data before we move to the client. The RTAC project is already configured for this example. Its single command uses address eleven, with the output command type set to Direct. This matches the Direct Execute mode supported by our server. The client also has the plant measurements in its point list. When we expand daily energy, we can see the value received from N3uron. This shows the read side of the example, with the existing plant tag exposed through our server configuration. We now move to the command in the RTAC. Its command fields are visible in the online view. We prepare the command value here, then use the client to send it to N3uron. In N3uron, the command tag is still false at this point. We return to the RTAC and send the command.
[06:02] The next view shows the result. The command tag now shows true, with an updated timestamp. The command reaches the tag through the IEC 104 Server. We return to the RTAC to inspect its values. Our example shows both directions of exchange, measurements sent out and a command received. In the server configuration, we use CSV to add the remaining points. Save CSV creates a file that we can edit. Load CSV brings the changes back into N3uron. This makes changes to many points easier. Here, we load a file prepared for this plant. We confirm the separator, and the point list appears in the group. The file contains the tag paths, data types, and addresses. We can see the additional KPIs, then save and apply the configuration.
[07:05] The real-time logs show the communication as it happens. Here, we filter the view to the IEC 104 Server and display Trace messages. We can follow the protocol activity in this view while the RTAC exchanges data with the server. We return to the client and look through the measurements. The point list now lets us inspect the other KPIs as well. The real-time tag view shows the values inside N3uron, while the RTAC view shows the values on the client side. We move between these views as we inspect the exchange. The logs give us another view of the same connection. Together, these screens help us investigate the configuration and the data that is being transferred. We can reuse a configuration that we already checked.
[08:02] Here, we drag the device into the Templates panel. The new template contains the device and its point mappings. We expose the common address and event timestamp mode as custom properties. These are values that can change between instances of the template. The rest of the structure stays in the template definition. This gives us one reusable device configuration, with the properties we need to set separately for each instance. Our second device comes from this template. We set its common address to two, with its own timestamp mode. The N3uron template system supports composition and inheritance. Composition lets us build larger configurations from smaller templates. Templates can represent servers, devices, information object groups, or individual information objects. Nested templates can inherit properties from a higher level.
[09:03] Devices can expose different tag groups, with different timestamps or interrogation groups. Like other N3uron modules, IEC 104 Server offers unlimited servers, devices, and information objects, or mapped tags. The configuration can follow our application, with separate devices for different plant areas. The Knowledge Base provides detailed information about the settings covered in this example, including devices, data types, interrogation groups, and supported protocol types. For additional guidance, you can use the built-in help in WebUI to learn more about each property. We also recommend N3uron Skills, which you can use with your preferred compatible AI agent. They can assist with configuration, troubleshooting, and generating import-ready CSV files from technical documentation, simplifying bulk configuration tasks.
[10:07] You can download N3uron Skills and find the setup guide in our Knowledge Base. Thanks for watching!
N3uron software is an AI-ready Industrial DataOps Platform that streamlines the flow of data between industrial systems and business applications, either on-premise or in the cloud. N3uron provides an out-of-the-box solution for data standardization, normalization and contextualization, seamless integration with industrial and IT systems, efficient information management, and unparalleled scalability and security. The N3uron platform makes it easier for operations teams to aggregate, manage and analyze industrial data, resulting in enhanced productivity and informed decision-making. Whether you're looking to optimize your operations, reduce downtime or improve product quality, the N3uron platform is the answer.
CONTRIBUTING MEMBER
N3uron is a Contributing Member of the Eclipse Foundation, actively participating in the development of their robust ecosystem. By leveraging EF technologies, we offer innovative products and services that drive our corporate strategy forward. N3uron is Sparkplug Compatible Software.


DLMS® UA MEMBER
N3uron is a member of the DLMS® User Association, the global community that drives standardization in the energy and water industry. Being part of the DLMS UA represents N3uron's commitment to advancing smart metering and energy management solutions.
FOLLOW US
N3uron Connectivity Systems • Paseo de la Castellana, 257, South Tower, 1st floor; Madrid, 28046, Spain • +34 911 841 938 • [email protected]
N3uron software is an AI-ready Industrial DataOps Platform that streamlines the flow of data between industrial systems and business applications, either on-premise or in the cloud. N3uron provides an out-of-the-box solution for data standardization, normalization and contextualization, seamless integration with industrial and IT systems, efficient information management, and unparalleled scalability and security. The N3uron platform makes it easier for operations teams to aggregate, manage and analyze industrial data, resulting in enhanced productivity and informed decision-making. Whether you're looking to optimize your operations, reduce downtime or improve product quality, the N3uron platform is the answer.
CONTRIBUTING MEMBER
N3uron is a Contributing Member of the Eclipse Foundation, actively participating in the development of their robust ecosystem. By leveraging EF technologies, we offer innovative products and services that drive our corporate strategy forward. N3uron is Sparkplug Compatible Software.


CONTRIBUTING MEMBER
N3uron is a Contributing Member of the Eclipse Foundation, actively participating in the development of their robust ecosystem. By leveraging EF technologies, we offer innovative products and services that drive our corporate strategy forward. N3uron is Sparkplug Compatible Software.
FOLLOW US
N3uron Connectivity Systems • Paseo de la Castellana, 257, South Tower, 1st floor; Madrid, 28046, Spain • +34 911 841 938 • [email protected]
N3uron software is an AI-ready Industrial DataOps Platform that streamlines the flow of data between industrial systems and business applications, either on-premise or in the cloud. N3uron provides an out-of-the-box solution for data standardization, normalization and contextualization, seamless integration with industrial and IT systems, efficient information management, and unparalleled scalability and security. The N3uron platform makes it easier for operations teams to aggregate, manage and analyze industrial data, resulting in enhanced productivity and informed decision-making. Whether you're looking to optimize your operations, reduce downtime or improve product quality, the N3uron platform is the answer.
CONTRIBUTING MEMBER
N3uron is a Contributing Member of the Eclipse Foundation, actively participating in the development of their robust ecosystem. By leveraging EF technologies, we offer innovative products and services that drive our corporate strategy forward. N3uron is Sparkplug Compatible Software.


DLMS® UA MEMBER
N3uron is a member of the DLMS® User Association, the global community that drives standardization in the energy and water industry. Being part of the DLMS UA represents N3uron's commitment to advancing smart metering and energy management solutions.
FOLLOW US
N3uron Connectivity Systems • Paseo de la Castellana, 257, South Tower, 1st floor; Madrid, 28046, Spain • +34 911 841 938 • [email protected]